Customization: | Available |
---|---|
After-sales Service: | 1years or 2000hours |
Warranty: | 1years or 2000hours |
Suppliers with verified business licenses
High reliability. Low operating costs. Mainly used in large IPP projects, up to 100 MWel.
(1)TCG 2032 V12 gas engine not available for biogas.
MWM Gas Engine TCG 2032B V16 with Fast Ramp-Up Option
High Reliability. Low Operating Costs - MWM Gas Engine TCG 2032.
High Availability - MWM Gas Engine TCG 2032
Low Installation Costs - MWM Gas Engine TCG 2032
Short Project Period - MWM Gas Engine TCG 2032
Lower Service Costs - MWM Gas Engine TCG 2032
Performance Data - MWM Gas Engine TCG 2032
Specifications and Service Intervals - MWM Gas Engine TCG 2032
Brochure - MWM Gas Engine TCG 2032
The MWM gas engines of the TCG 2032 series are perfectly geared to the challenges of a dynamic market environment. In the power range of 3,000 - 4,500 kWel reliability, flexibility, efficiency and environmental compatibility are ensured along with low life-cycle costs. In this way, they meet the high requirements of a wide range of applications and are highly profitable.
(2) Available for all TCG 2032B V16 standard voltages 6000 V to 11 kV @50Hz, only for natural gas.
TCG 2032 V12 R = Optimized for high total efficiency |
|||
---|---|---|---|
Engine type | 50 Hz | 60 Hz** | |
Electrical output | kW | 3333 | 3000 |
Mean effective pressure | bar | 20.0 | 20.1 |
Thermal output ± 8% | kW | 2862 | 2539 |
Electrical efficiency | % | 43.9 | 43.9 |
Thermal efficiency | % | 42.6 | 42.1 |
Total efficiency | % | 86.5 | 86.0 |
Power to heat ratio*** | 1.03 | 1.04 |
TCG 2032 V16 R = Optimized for high total efficiency |
TCG 2032B V16 R = Optimized for high total efficiency |
||||
---|---|---|---|---|---|
Engine type | 50 Hz | 60 Hz** | 50 Hz | 60 Hz** | |
Electrical output | kW | 4300 | 4000 | 4500 | 4050 |
Mean effective pressure | bar | 19.4 | 20.2 | 20.3 | 20.4 |
Thermal output ± 8% | kW | 3698 | 3411 | 3668 | 3252 |
Electrical efficiency | % | 44.1 | 43.8 | 44.6 | 44.3 |
Thermal efficiency | % | 42.7 | 42.4 | 43.1 | 42.6 |
Total efficiency | % | 86.8 | 86.2 | 87.7 | 86.9 |
Power to heat ratio*** | 1.03 | 1.03 | 1.03 | 1.04 |
* 5% O2 and dry exhaust gases
** On request
*** The power to heat ratio is calculated by dividing the electrical efficiency by the thermal efficiency. Please remember that this is a theoretical value that may deviate from actually measured values.
The values given in these tables are information purposes only and not binding. The information given in the offer is decisive. Other unit variants with other generators are available.
TCG 2032 V16 X = Optimized for operation with biogases |
|||
---|---|---|---|
Engine type | 50 Hz | 60 Hz** | |
Electrical output | kW | 3770 | 3510 |
Mean effective pressure | bar | 17.0 | 17.0 |
Thermal output ± 8% | kW | 3196 | 2880 |
Electrical efficiency | % | 43.0 | 43.3 |
Thermal efficiency | % | 41.9 | 40.6 |
Total efficiency | % | 84.9 | 83.9 |
Power to heat ratio*** | 1.03 | 1.07 |
* 5% O2 and dry exhaust gases
** On request
*** The power to heat ratio is calculated by dividing the electrical efficiency by the thermal efficiency. Please remember that this is a theoretical value that may deviate from actually measured values.
The values given in this table are information purposes only and not binding. The information given in the offer is decisive. Other unit variants with other generators are available.
TCG 2032 V12 | TCG 2032 V16 | ||||
---|---|---|---|---|---|
Engine type | 50 Hz | 60 Hz* | 50 Hz | 60 Hz* | |
Length | mm | 7860 | 8000 | 9271 | 9420 |
Width | mm | 2660 | 2790 | 2790 | 2790 |
Height | mm | 3390 | 3390 | 3390 | 3390 |
Dry weight genset | kg | 43100 | 49780 | 51200 | 52400 |
Bore / stroke | mm | 260/320 | 260/320 | 260/320 | 260/320 |
* On request
The values given in this table are information purposes only and not binding. The information given in the offer is decisive. Other unit variants with other generators are available.
First service (check valve clearance)* | Mixture cooler cleaning | Cylinder head inspection | Major overhaul | |
---|---|---|---|---|
Natural gas | 4,000 oh | 20,000 oh | 40,000 oh | 80,000 oh |
* "after commissioning (E10)"
The values given in this table are information purposes only and not binding. The information given in the offer is decisive. Other unit variants with other generators are available.